Ground Wire Size Chart

Equipment ground size by breaker, the grounding electrode conductor for a service, and the ground for upsized wire.

Minimum equipment grounding conductor for standard breakers from 15 to 200 A, from NEC Table 250.122.
Breaker Copper Aluminum
15 A14 AWG12 AWG
20 A12 AWG10 AWG
25 A10 AWG8 AWG
30 A10 AWG8 AWG
35 A10 AWG8 AWG
40 A10 AWG8 AWG
45 A10 AWG8 AWG
50 A10 AWG8 AWG
60 A10 AWG8 AWG
70 A8 AWG6 AWG
80 A8 AWG6 AWG
90 A8 AWG6 AWG
100 A8 AWG6 AWG
110 A6 AWG4 AWG
125 A6 AWG4 AWG
150 A6 AWG4 AWG
175 A6 AWG4 AWG
200 A6 AWG4 AWG

Ground for upsized wire

Upsizing the circuit wires, for voltage drop for example, upsizes the ground in proportion (NEC 250.122(B); 2026: 250.122(D)).

Metal

Table 250.122: all ratings

Minimum equipment grounding conductor by the rating of the breaker or fuse ahead of the circuit (not exceeding), NEC Table 250.122. The aluminum column includes copper-clad aluminum. Sizes from 250 are kcmil.
Breaker or fuse rating Copper Aluminum
15 A14 AWG12 AWG
20 A12 AWG10 AWG
60 A10 AWG8 AWG
100 A8 AWG6 AWG
200 A6 AWG4 AWG
300 A4 AWG2 AWG
400 A3 AWG1 AWG
500 A2 AWG1/0 AWG
600 A1 AWG2/0 AWG
800 A1/0 AWG3/0 AWG
1000 A2/0 AWG4/0 AWG
1200 A3/0 AWG250 kcmil
1600 A4/0 AWG350 kcmil
2000 A250 kcmil400 kcmil
2500 A350 kcmil600 kcmil
3000 A400 kcmil600 kcmil
4000 A500 kcmil750 kcmil
5000 A700 kcmil1250 kcmil
6000 A800 kcmil1250 kcmil

Grounding electrode conductor: Table 250.66

Grounding electrode conductor by the largest ungrounded service-entrance conductor (parallel sets summed), NEC Table 250.66. A GEC to a ground rod need not be larger than 6 AWG copper; to a concrete-encased electrode, 4 AWG copper (250.66(A), (B)).
Largest service conductor, copper Largest service conductor, aluminum GEC copper GEC aluminum
2 or smaller1/0 or smaller8 AWG6 AWG
1 or 1/02/0 or 3/06 AWG4 AWG
2/0 or 3/04/0 or 2504 AWG2 AWG
Over 3/0 through 350Over 250 through 5002 AWG1/0 AWG
Over 350 through 600Over 500 through 9001/0 AWG3/0 AWG
Over 600 through 1100Over 900 through 17502/0 AWG4/0 AWG
Over 1100Over 17503/0 AWG250 kcmil

Use this next

The ground wire in a branch circuit or feeder is the equipment grounding conductor, and NEC Table 250.122 sizes it by the rating of the breaker or fuse ahead of the circuit, not by the size of the hot wires. Each row covers every rating up to its own, so you read the first row at or above your breaker. So the sizes come in steps: a 15 A circuit takes a 14 AWG copper ground and a 20 A circuit 12 AWG, but every breaker from 25 to 60 A takes 10 AWG, 70 to 100 A takes 8 AWG and 110 to 200 A takes 6 AWG. The aluminum column, which also covers copper-clad aluminum, is the next size up at each step, and its footnote points to 250.120 for where aluminum grounds may be run.

The table is a minimum. A note to it says the ground has to be larger where that is needed for an effective ground-fault path, and 250.122(A) says it never has to be larger than the circuit conductors supplying the equipment.

Factory cable already follows the table. Southwire's and Cerrowire's NM-B specs give 14/2 a 14 AWG ground, 12/2 a 12 AWG ground and 10/2 a 10 AWG ground. 8/2 and 6/2 carry a 10 AWG ground too, which is enough: 8/2 is rated 40 A and 6/2 is rated 55 A at 60 °C, both inside the 25 to 60 A row. The 4/3 and 2/3 cables carry 8 AWG, the 70 to 100 A size.

Upsizing the hot wires changes the ground. When the ungrounded conductors are made larger than the minimum for any reason other than the ampacity adjustment and correction of 310.15(B) and (C), such as voltage drop on a long run, a wire-type ground has to grow in proportion to their circular-mil area. A 20 A circuit needs 12 AWG copper. Run it in 10 AWG and the hots grow from 6,530 to 10,380 circular mils, so the 12 AWG ground grows by the same ratio to 10,380: a 10 AWG ground, which is what 10/2 NM-B has.

The calculator uses the exact area ratio, with no rounding. On a 60 A circuit that needs 6 AWG copper but is run in 4 AWG, the ratio is 41,740 ÷ 26,240, or 1.5907. Applied to the 10 AWG ground's 10,380 circular mils, it gives about 16,511, just over the 16,510 of 8 AWG, so the result is 6 AWG. Rounding the ratio to 1.59 would give 16,504 and an 8 AWG ground. The calculator shows the exact, conservative size. An exception lets a qualified person size the ground to give an effective ground-fault path instead, and whether it applies is for the electrician or inspector to decide.

The grounding electrode conductor is a different wire. It runs from the service, from a building supplied by a feeder or from a separately derived system to the grounding electrodes, such as ground rods or a concrete-encased electrode. Table 250.66 sizes it by the largest ungrounded service-entrance conductor, with parallel sets added together, not by the main breaker. 250.66 then sets caps, not minimums: the part that runs only to rods, pipes or plates need not be larger than 6 AWG copper or 4 AWG aluminum or copper-clad aluminum, the part that runs only to a concrete-encased electrode need not be larger than 4 AWG copper, and the part to a ground ring need not be larger than the ring conductor.

Some nearby conductors use neither table. Since the 2014 edition, the main bonding jumper, the system bonding jumper, supply-side bonding jumpers and the grounded conductor are sized from Table 250.102(C)(1), not Table 250.66; bonding jumpers between electrodes do use 250.66. The proportional rule is 250.122(B) in the 2023 NEC and 250.122(D) in 2026, where the section was reorganized with no technical change, and both tables have the same values in both editions. The 2026 edition moves systems over 1000 V AC or 1500 V DC to Article 270, so the tables on this page are the ones for systems up to those voltages. Your local code edition and its amendments apply.

Frequently asked questions

What size ground wire for a 100 amp subpanel?

8 AWG copper or 6 AWG aluminum, from the 100 A row of Table 250.122. The ground in the feeder is sized by the 100 A breaker that feeds the subpanel. If the feeder conductors are upsized beyond what 100 A needs, for voltage drop for example, the ground grows in proportion: a feeder that needs 3 AWG copper but is run in 1 AWG needs a 4 AWG copper ground.

What size ground wire for 200 amp service?

4 AWG copper, or 2 AWG aluminum, for the grounding electrode conductor of a 200 A dwelling service in 2/0 copper or 4/0 aluminum, the 310.12 sizes. That conductor comes from Table 250.66, sized by the service conductors. Where it runs only to ground rods, it need not be larger than 6 AWG copper; to a concrete-encased electrode, 4 AWG copper. A 200 A feeder to a subpanel is different: its equipment ground is 6 AWG copper or 4 AWG aluminum, from Table 250.122.

What size ground for a 50 amp circuit?

10 AWG copper or 8 AWG aluminum. A 50 A breaker falls in the 60 A row of Table 250.122, which covers every rating from 25 to 60 A. 6/2 NM-B, rated 55 A at 60 °C, comes with a 10 AWG ground for that reason.

Does the ground wire need to be the same size as the hot wires?

No. It is sized by the breaker, so it matches the hots at 15, 20 and 30 A but is smaller above that: 8/2 NM-B on a 40 A breaker has a 10 AWG ground, and a 200 A feeder takes a 6 AWG copper ground. It never has to be larger than the circuit conductors (250.122(A)). It does grow when the hots are upsized for reasons other than ampacity adjustment and correction.

Do I need a bigger ground if I upsize the wire?

Yes, when the hots are upsized for any reason other than the adjustment and correction factors of 310.15(B) and (C), the ground grows in proportion to their circular-mil area. A 20 A circuit run in 10 AWG instead of 12 AWG copper needs a 10 AWG ground. On a 60 A circuit run in 4 AWG instead of 6 AWG, the exact ratio gives a 6 AWG ground rather than 10 AWG. A qualified person may instead size the ground for an effective ground-fault path, which the electrician or inspector decides.