Conduit Fill Calculator

How full your conduit is, whether the wires fit under NEC Chapter 9, and the smallest size that holds them.

Wires include the grounding conductor

How many THHN wires fit in EMT (electrical metallic tubing)

Most THHN / THWN-2 wires of one size by trade size, from NEC Chapter 9 Tables 1, 4 and 5 (40% fill for three or more wires).
Wire 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 3-1/2 in 4 in
14 AWG1222356184138241364476608
12 AWG916264561101176266347443
10 AWG51016283863111167219279
8 AWG3691622366496126161
6 AWG247111626466991116
4 AWG1247101628435671
3 AWG113681324364760
2 AWG113571120304051
1 AWG11145815222937
1/0 AWG11134712192532
2/0 AWG01123610162026
3/0 AWG0111358131722
4/0 AWG0111247111418

How many THHN wires fit in PVC Schedule 40 (and HDPE)

Most THHN / THWN-2 wires of one size by trade size, from NEC Chapter 9 Tables 1, 4 and 5 (40% fill for three or more wires).
Wire 1/2 in 3/4 in 1 in 1-1/4 in 1-1/2 in 2 in 2-1/2 in 3 in 3-1/2 in 4 in
14 AWG1121346082135193299401517
12 AWG81525435999141218293377
10 AWG591527376289137184238
8 AWG3591621365179106137
6 AWG14611152637577799
4 AWG124791622354761
3 AWG113681319304051
2 AWG113571116253343
1 AWG11135812182532
1/0 AWG11134710152127
2/0 AWG0112368131722
3/0 AWG0111357111418
4/0 AWG011124691215

Use this next

Choose the conduit type and trade size, then enter each group of wires: how many, the size and the insulation. Count every wire in the run, the ground included. Chapter 9 Note 3 counts equipment grounding and bonding conductors in the fill at their actual size, bare or insulated. The result gives the percent full, the limit that applies, the smallest trade size that holds the same wires, and a row for every trade size to show the margin. Take three 12 AWG THHN and one 10 AWG bare stranded ground in 1/2 in EMT: they total 0.0505 sq in, which is 16.6% of the tube's 0.304 sq in, inside the 40% limit of 0.122 sq in.

The limit depends on how many wires share the conduit. NEC Chapter 9 Table 1 allows 53% of the inside area for one conductor, 31% for two and 40% for three or more. The limits leave room to pull wire around bends without scraping the insulation, and air around the conductors to carry off the heat they make under load. Two wires get the lowest share of the three. A nipple, a piece 24 in or shorter between enclosures, is allowed 60% under Note 4, whatever the number of wires.

Insulation changes the count as much as gauge does. Table 5 gives 12 AWG THHN an area of 0.0133 sq in and 12 AWG XHHW 0.0181 sq in, more than a third larger. At 40% of 1/2 in EMT, that is the difference between 9 THHN and 6 XHHW. THW and TW have the same 12 AWG area as XHHW. The insulation type is printed along the wire's jacket.

Trade size is a name rather than a measurement, and the inside area varies with the conduit type. 1/2 in EMT has 0.304 sq in inside; PVC Schedule 40 has 0.285, and Schedule 80, with its thicker wall, 0.217. That takes the 12 AWG THHN count from 9 in EMT to 8 in Schedule 40 and 6 in Schedule 80. The tables below the calculator give THHN counts for every size of EMT and of PVC Schedule 40, which Table 4 lists together with HDPE. The calculator covers the other types: rigid and intermediate metal conduit, flexible and liquidtight conduit, and ENT.

When every wire is the same size, Note 7 lets a count that comes out at .8 or more round up to the next whole wire. With 8 AWG THHN in 3/4 in EMT, the 40% area holds 5.82 wires, so the count is 6. Mixed sizes don't round: their areas are added, and the total has to be within the limit. The NEC's Annex C tables list same-size counts, and this calculator matches them in 52 of the 53 counts checked. The exception is 6 AWG THHN in 1-1/4 in EMT. Table C.1 shows 12, while the printed Table 4 figure, 0.598 sq in at 40%, divided by 0.0507 sq in a wire comes to 11.79, so the calculator says 11. It keeps the printed area, the conservative choice; whether the Annex C count is accepted is the inspector's call.

Passing fill doesn't settle the wire size. With more than three current-carrying conductors in one raceway, NEC 310.15(C)(1) lowers their ampacity to 80% for 4 to 6 and 70% for 7 to 9. Nine 12 AWG THHN fit in 1/2 in EMT, but if all nine carry current, each is held to 70% of its table ampacity. Grounding conductors don't count toward that. The calculator flags the adjustment when more than three insulated wires are entered, without working it out.

Cables are a separate case. Note 9 counts a multiconductor cable as one conductor, and an oval cable as a circle the width of its widest dimension. Cable sizes aren't in the NEC tables, so this calculator handles individual wires only. Bends, pull length and local amendments matter too; an electrician sizes the conduit for the run, and the inspector decides whether it passes.

Frequently asked questions

How many 12 gauge wires can go in 1/2 inch EMT?

9 THHN or 6 XHHW, under the 40% limit for three or more wires. If one of them is an insulated 12 AWG ground, it is one of the nine. In a nipple of 24 in or less, where 60% is allowed, the THHN count rises to 13.

How many 12 gauge wires fit in 3/4 PVC?

15 THHN in Schedule 40 and 12 in Schedule 80. Schedule 80's thicker wall leaves 0.409 sq in inside, against 0.508 for Schedule 40. In XHHW the counts are 11 and 9.

What is the 40% conduit fill rule?

Three or more wires may take up to 40% of a conduit's inside area, under NEC Chapter 9 Table 1. The wire areas, insulation included, come from Table 5, or from the Table 8 diameter for bare wire; they are added and compared with the conduit's Table 4 area. One wire may take 53%, two 31%, and any number in a nipple of 24 in or shorter 60%.

Does the ground wire count in conduit fill?

Yes. Chapter 9 Note 3 counts equipment grounding and bonding conductors at their actual size. A bare ground is figured from its Table 8 diameter: 10 AWG bare stranded is 0.116 in across, about 0.0106 sq in. The ground isn't counted for the ampacity adjustment on more than three current-carrying conductors, since it carries no current in normal use.

How is conduit fill figured with mixed wire sizes?

By adding the area of every wire and comparing the total with the allowed area. Two 10 AWG THHN, three 12 AWG THHN and a 10 AWG bare stranded ground come to 0.0927 sq in, 30.5% of 1/2 in EMT and within the 40% limit. The Note 7 round-up applies only when all the wires are the same size.