Conduit Fill Chart

The most wires of one size in each conduit, by NEC Chapter 9. For a mix of sizes, use the conduit fill calculator.

EMT (electrical metallic tubing): THHN wires

Most THHN / THWN-2 wires of one size by trade size (NEC Chapter 9 Tables 1, 4 and 5; 40% fill for three or more).
Wire1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in2-1/2 in3 in3-1/2 in4 in
14 AWG1222356184138241364476608
12 AWG916264561101176266347443
10 AWG51016283863111167219279
8 AWG3691622366496126161
6 AWG247111626466991116
4 AWG1247101628435671
3 AWG113681324364760
2 AWG113571120304051
1 AWG11145815222937
1/0 AWG11134712192532
2/0 AWG01123610162026
3/0 AWG0111358131722
4/0 AWG0111247111418

PVC Schedule 40 (and HDPE): THHN wires

Most THHN / THWN-2 wires of one size by trade size (NEC Chapter 9 Tables 1, 4 and 5; 40% fill for three or more).
Wire1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in2-1/2 in3 in3-1/2 in4 in
14 AWG1121346082135193299401517
12 AWG81525435999141218293377
10 AWG591527376289137184238
8 AWG3591621365179106137
6 AWG14611152637577799
4 AWG124791622354761
3 AWG113681319304051
2 AWG113571116253343
1 AWG11135812182532
1/0 AWG11134710152127
2/0 AWG0112368131722
3/0 AWG0111357111418
4/0 AWG011124691215

PVC Schedule 80: THHN wires

Most THHN / THWN-2 wires of one size by trade size (NEC Chapter 9 Tables 1, 4 and 5; 40% fill for three or more).
Wire1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in2-1/2 in3 in3-1/2 in4 in
14 AWG917285170118169265358464
12 AWG61220375186124193261338
10 AWG471323325478122164213
8 AWG247131831457095123
6 AWG1359132232516889
4 AWG113681420314254
3 AWG113571217263546
2 AWG112461014223039
1 AWG01134710162229
1/0 AWG0112369141824
2/0 AWG0111357111520
3/0 AWG011124691317
4/0 AWG001113581014

RMC (rigid metal conduit): THHN wires

Most THHN / THWN-2 wires of one size by trade size (NEC Chapter 9 Tables 1, 4 and 5; 40% fill for three or more).
Wire1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in2-1/2 in3 in3-1/2 in4 in
14 AWG1322366385140200309412531
12 AWG916264662102146225301387
10 AWG6101729396492142189244
8 AWG3691622375382109140
6 AWG247121627385979101
4 AWG1247101623364862
3 AWG113681420314153
2 AWG113571117263444
1 AWG11145812192533
1/0 AWG11134710162127
2/0 AWG0112368131823
3/0 AWG0111357111519
4/0 AWG011124691216

IMC (intermediate metal conduit): THHN wires

Most THHN / THWN-2 wires of one size by trade size (NEC Chapter 9 Tables 1, 4 and 5; 40% fill for three or more).
Wire1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in2-1/2 in3 in3-1/2 in4 in
14 AWG1424396891149211326436562
12 AWG1017294967109154238318410
10 AWG6111831426997150200258
8 AWG36101824395686115149
6 AWG247131728406283107
4 AWG1348111725385166
3 AWG124691521324356
2 AWG113571217273647
1 AWG11245913202735
1/0 AWG11134811172329
2/0 AWG1113469141924
3/0 AWG0112357121620
4/0 AWG011124691317

FMC (flexible metal conduit): THHN wires

Most THHN / THWN-2 wires of one size by trade size (NEC Chapter 9 Tables 1, 4 and 5; 40% fill for three or more).
Wire1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in2-1/2 in3 in3-1/2 in4 in
14 AWG1322335276134202291396518
12 AWG91624385698147212289378
10 AWG6101524356293134182238
8 AWG3691420355377105137
6 AWG24610142538557699
4 AWG124691624344661
3 AWG113571320293951
2 AWG113461117243343
1 AWG11134812182432
1/0 AWG11124710152027
2/0 AWG0111369121722
3/0 AWG0111257101418
4/0 AWG011114681215

LFMC (liquidtight flexible metal conduit): THHN wires

Most THHN / THWN-2 wires of one size by trade size (NEC Chapter 9 Tables 1, 4 and 5; 40% fill for three or more).
Wire1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in2-1/2 in3 in3-1/2 in4 in
14 AWG1322366381134201308401523
12 AWG91626465997147225292381
10 AWG6101629376192141184240
8 AWG3691621355381106138
6 AWG247121525385976100
4 AWG124791523364761
3 AWG113681320304052
2 AWG113571117263344
1 AWG11145812192532
1/0 AWG11134710162127
2/0 AWG0112368131723
3/0 AWG0111357111419
4/0 AWG011124691215

LFNC-B (liquidtight flexible nonmetallic conduit): THHN wires

Most THHN / THWN-2 wires of one size by trade size (NEC Chapter 9 Tables 1, 4 and 5; 40% fill for three or more).
Wire1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in
14 AWG1322366381134
12 AWG91626465997
10 AWG61016293761
8 AWG369162135
6 AWG247121525
4 AWG1247915
3 AWG1136813
2 AWG1135711
1 AWG111458
1/0 AWG111347
2/0 AWG011236
3/0 AWG011135
4/0 AWG011124

ENT (electrical nonmetallic tubing): THHN wires

Most THHN / THWN-2 wires of one size by trade size (NEC Chapter 9 Tables 1, 4 and 5; 40% fill for three or more).
Wire1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in
14 AWG1121346082135
12 AWG81525435999
10 AWG5915273762
8 AWG359162136
6 AWG146111526
4 AWG1247916
3 AWG1136813
2 AWG1135711
1 AWG111358
1/0 AWG111347
2/0 AWG011236
3/0 AWG011135
4/0 AWG011124

EMT (electrical metallic tubing): XHHW wires

Most XHHW / XHHW-2 wires of one size by trade size (NEC Chapter 9 Tables 1, 4 and 5).
Wire1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in2-1/2 in3 in3-1/2 in4 in
14 AWG81525435896168254332424
12 AWG61119334574129195255326
10 AWG581424335596145190243
8 AWG2581318305381105135
6 AWG136101322396078100
4 AWG1247101628435672
3 AWG113681424364861
2 AWG113571120314051
1 AWG11145815233038
1/0 AWG11134713192532
2/0 AWG01123610162127
3/0 AWG0111359131722
4/0 AWG0111247111418

PVC Schedule 40 (and HDPE): XHHW wires

Most XHHW / XHHW-2 wires of one size by trade size (NEC Chapter 9 Tables 1, 4 and 5).
Wire1/2 in3/4 in1 in1-1/4 in1-1/2 in2 in2-1/2 in3 in3-1/2 in4 in
14 AWG81424415794135209280361
12 AWG61118324472103160215277
10 AWG481324325477119160206
8 AWG247131830436689115
6 AWG13510132232496685
4 AWG124791623354861
3 AWG113681319304052
2 AWG113571116253444
1 AWG11135812192532
1/0 AWG11134710162127
2/0 AWG0112368131723
3/0 AWG0111357111419
4/0 AWG011124691215

Conduit inside area at 40% fill

Square inches available to three or more wires (40% of the inside area, NEC Chapter 9 Table 4). A dash: that trade size isn't listed for the type.
Trade sizeEMTPVC40PVC80RMCIMCFMCLFMCLFNC-BENT
1/2 in0.1220.1140.0870.1250.1370.1270.1250.1250.114
3/4 in0.2130.2030.1640.2200.2350.2130.2160.2160.203
1 in0.3460.3330.2750.3550.3840.3270.3490.3490.333
1-1/4 in0.5980.5810.4950.6100.6590.5110.6110.6110.581
1-1/2 in0.8140.7940.6840.8290.8900.7430.7920.7920.794
2 in1.3421.3161.1501.3631.4521.3071.2981.2981.316
2-1/2 in2.3431.8781.6471.9462.0541.9631.953--
3 in3.5382.9072.5773.0003.1692.8272.990--
3-1/2 in4.6183.8953.4754.0044.2343.8483.893--
4 in5.9015.0224.5035.1535.4525.0275.077--

Use this next

Pick the conduit type from the links at the top, find your wire size in the left column and read across to the trade size. The number is the most wires of that one size and insulation the conduit holds: 16 of 12 AWG THHN in 3/4 in EMT, for example, or 16 of 10 AWG THHN in 1 in EMT. When a run carries more than one size, say 10 AWG for one circuit and 12 AWG for another, the chart can't add them up; the conduit fill calculator works out the total.

Most cells come from the 40% limit for three or more wires. Where three won't fit, the count drops to the smaller limits for two wires and for one, so a 2 or a 1 in a table is set by those, and a 0 means not even one wire of that size fits. 6 AWG THHN is 2 in 1/2 in EMT but 1 in 1/2 in PVC Schedule 40, and a 4/0 THHN doesn't go in 1/2 in EMT at all.

The same trade size holds different counts from one conduit type to the next because each type has its own inside area in Chapter 9 Table 4, listed at 40% in the areas table below. At 1/2 in, IMC has the most room, 0.137 sq in, and PVC Schedule 80 the least, 0.087, against 0.122 for EMT; 12 AWG THHN runs from 10 in IMC down to 6 in Schedule 80. Flexible metal conduit keeps pace with EMT in the small sizes and falls behind in the larger ones: both hold 16 of 12 AWG THHN at 3/4 in, while at 1-1/4 in EMT holds 45 and FMC 38. ENT and LFNC-B are listed only up to 2 in, so their tables stop there.

THHN tables cover all nine types, and XHHW tables cover EMT and PVC Schedule 40. The difference between the two is largest in small wire. Table 5 lists 14 AWG XHHW at about 43% more area than 14 AWG THHN, so 3/4 in EMT holds 22 THHN but 15 XHHW. At 10 AWG the gap is about 15%, and 1 in EMT holds 16 THHN against 14 XHHW. From 4 AWG up, Table 5 lists XHHW as slightly smaller than THHN, and its count is the same or one higher: 4 in EMT takes 71 of 4 AWG THHN or 72 of 4 AWG XHHW.

Every count here applies the NEC's rounding for wires of one size: when the division leaves 0.8 of a wire or more, Chapter 9 Note 7 lets that last wire count. The area of 1 in EMT works out to 6.82 wires of 6 AWG THHN, so the table shows 7, and 1/2 in PVC Schedule 80 works out to 8.97 of 14 AWG THHN, shown as 9. Checked against the NEC's Annex C tables, the same method reproduces 52 of 53 counts. The one that differs is 6 AWG THHN in 1-1/4 in EMT: Annex C gives 12, while the printed Table 4 area gives 11.79 wires, just short of the round-up, so this chart shows 11. If the job depends on that twelfth wire, ask the inspector which figure they accept.

A count in the chart is a limit on space, not on current. When more than three current-carrying conductors share a raceway, NEC 310.15(C)(1) reduces their ampacity: to 80% for 4 to 6 conductors and 70% for 7 to 9. Sixteen 12 AWG THHN fit in 3/4 in EMT, but sixteen current-carrying conductors are more than the 7 to 9 that take 70%, so look up the adjustment for that number before settling on the wire size.

Count the ground before you read the chart. Equipment grounding and bonding conductors take up space under Chapter 9 Note 3, the same as the circuit wires. In 3/4 in EMT, fifteen 12 AWG THHN circuit wires and a 12 AWG THHN ground make sixteen, the most the table allows. A bare ground has a different area from an insulated wire of the same gauge, so a run with a bare ground is a mixed run: use the calculator.

Frequently asked questions

How many 12 gauge wires fit in 3/4 EMT?

16 THHN or 11 XHHW, at the 40% limit for three or more wires. A 12 AWG THHN ground counts as one of the 16.

How many 10 gauge wires fit in 1 inch EMT?

16 THHN or 14 XHHW. In 1 in PVC the THHN count is 15 for Schedule 40 and 13 for Schedule 80.

How many wires fit in 1/2 inch flex?

9 of 12 AWG THHN in 1/2 in flexible metal conduit (FMC), 13 of 14 AWG and 6 of 10 AWG. The 12 AWG count is also 9 in 1/2 in liquidtight, both LFMC and LFNC-B.

What is the difference between PVC Schedule 40 and 80 fill?

Schedule 80 has less inside area at every trade size, so it holds fewer wires. At 1/2 in its 40% area is 0.087 sq in against 0.114 for Schedule 40, about 24% less; at 4 in the gap is about 10%, 4.503 against 5.022. In 2 in conduit that is 86 of 12 AWG THHN in Schedule 80 and 99 in Schedule 40.

Why does the chart show 0 for some wire sizes?

Because not even one wire of that size fits. A single wire may fill up to 53% of the inside area, and one 4/0 THHN, at 0.3237 sq in, is larger than 53% of 1/2 in EMT, 0.161 sq in. EMT takes a 4/0 THHN from 3/4 in up.