200 Amp Wire Size

2/0 AWG copper or 4/0 AWG aluminum

For a 200 A dwelling service or main feeder that carries the whole home's load, with conductors and terminals rated 75 °C: NEC 310.12 sizes them at 83% of the rating (166 A). On a 200 A breaker that isn't a dwelling service, such as a feeder to a subpanel serving part of the home, the full 200 A applies: 3/0 AWG copper at 75 °C, and aluminum larger than 4/0. Sizes larger than 4/0 are in kcmil, beyond these tables.

Smallest wire for a 200 A breaker, NEC 2026 Table 310.16 and 240.4(D). 30 °C ambient, up to three current-carrying conductors.
Wire and columnSmallest sizeAllowed amps
Copper, 60 °Cover 4/0
Copper, 75 °C3/0 AWG200 A
Aluminum, 60 °Cover 4/0
Aluminum, 75 °Cover 4/0

200 A dwelling service or main feeder

NEC 310.12 covers the service or main feeder that carries the whole home's load, on a 120/240 V single-phase system rated 100 to 400 A. It allows those conductors to be sized at 83% of the rating (166 A). With conductors rated 75 °C and 75 °C terminals, that is 2/0 AWG copper or 4/0 AWG aluminum. Conductors or cable limited to 60 °C take the 83% from the 60 °C column, giving 4/0 AWG copper or aluminum larger than 4/0. NM-B isn't made in these sizes (NEC 334.104 makes it only up to 2 AWG). The rule doesn't apply to a feeder to a subpanel that serves only part of the home, and your electrician or inspector confirms whether it applies to yours.

How length changes the answer

Recommended AWG for 200 A at 240 V single phase, by one-way length: the larger of the ampacity size and the size that keeps voltage drop within 3%.
Length, one way Copper, 60 °C Copper, 75 °C Aluminum, 60 °C Aluminum, 75 °C
25 ftover 4/03/0over 4/0over 4/0
50 ftover 4/03/0over 4/0over 4/0
75 ftover 4/03/0over 4/0over 4/0
100 ftover 4/03/0over 4/0over 4/0
150 ftover 4/03/0over 4/0over 4/0
200 ftover 4/03/0over 4/0over 4/0

Check your own circuit in the wire size calculator

Use this next

For a house on a 200 A service, NEC 310.12 gives 2/0 AWG copper or 4/0 AWG aluminum, as long as the conductors and the terminals they connect to are rated 75 °C. Neither size reaches 200 A by itself. In the 75 °C column of Table 310.16, 2/0 copper is rated 175 A and 4/0 aluminum 180 A. Both are more than 166 A, and 166 A is all 310.12 asks of a dwelling service, since it sets the minimum at 83% of the rating.

That smaller size has conditions. 310.12 applies to a one-family house, or to one dwelling unit in a two-family or multifamily building, supplied at 120/240 V single phase, with a service or feeder rated 100 to 400 A. The conductors also have to carry the unit's entire load. A 200 A service to a house meets those conditions, and so does a feeder that supplies everything the unit uses. A 200 A feeder from the main panel to a subpanel doesn't, however large the subpanel, because it carries only part of the load. That feeder is sized for the full 200 A.

At the full 200 A, Table 310.16 gives 3/0 copper in the 75 °C column, rated exactly 200 A with no margin. Every other column needs a size larger than 4/0. 4/0 copper is rated 195 A at 60 °C, and 4/0 aluminum is rated 150 A at 60 °C and 180 A at 75 °C. The answer is in kcmil instead. 250 kcmil copper, rated 215 A at 60 °C, covers the 60 °C copper case, and 250 kcmil aluminum, rated 205 A at 75 °C, covers the 75 °C aluminum case. Aluminum limited to 60 °C needs more than 250 kcmil, which is rated only 170 A in that column. Feeders come under NEC Article 215, and a feeder to a detached building also comes under Article 225. Continuous loads on a subpanel count at 125% (215.4(A)(1); 215.2(A)(1) in 2023).

The 2026 NEC added a condition to the 83% rule: Table 310.12(A) may be used only for conductors or cables rated 75 °C or more. Wire limited to 60 °C has to find 166 A in its own 60 °C column. At 200 A that takes copper to 4/0 and aluminum beyond it. The condition is new in 2026, and many areas still enforce the 2023 or 2020 edition. The inspector knows which edition applies where you are.

Service-entrance cable, type SE, is covered by NEC Article 338. Style SER is one style of it, and the cable's printed legend names both. Southwire stocks 4/0 aluminum SER with three 4/0 conductors and a 2/0 ground. Its spec sheet rates that cable 180 A at 75 °C and 205 A at 90 °C, the same values as Table 310.16. So 4/0 aluminum works as a 200 A dwelling service under 310.12, but as a feeder that has to carry the full 200 A it falls 20 A short in the 75 °C column.

Distance seldom changes a 200 A size. At 240 V and the full 200 A, 3/0 copper loses 6.01 V over 200 feet, which is 2.51%. It doesn't reach 3% until about 239 feet one way, so the length table shows 3/0 in the copper 75 °C column at every length. The cells that read "over 4/0" come from ampacity, not from length. The service sizes hold up too. Carrying 166 A for 200 feet, 2/0 copper drops 2.62% and 4/0 aluminum drops 2.72%. The 3% figure comes from an NEC informational note and is a recommendation, not a requirement.

This page doesn't decide whether a home needs 200 A rather than some other rating. That depends on a load calculation under Article 120 of the 2026 NEC (Article 220 in 2023), which is for the electrician and the inspector to settle. The sizes above assume the 200 A rating has already been decided.

Frequently asked questions

What size wire for 200 amp service?

2/0 AWG copper or 4/0 AWG aluminum, where the conductors and terminals are rated 75 °C and the service carries the whole home's load. NEC 310.12 sizes a dwelling service at 83% of its rating, which is 166 A. In the 75 °C column of Table 310.16, 2/0 copper is rated 175 A and 4/0 aluminum 180 A.

Is 4/0 aluminum good for 200 amps?

Yes for a home's 200 A service or main feeder with 75 °C conductors and terminals: 4/0 is the Table 310.12(A) aluminum size for 200 A. No for a 200 A feeder to a subpanel: 4/0 aluminum is rated 180 A at 75 °C, and the full-200 A size is 250 kcmil aluminum, rated 205 A. Putting a 180 A conductor on the next standard breaker size up falls under NEC 240.4(B) and its conditions. The tables here don't apply that rule, so the electrician or inspector decides whether it fits.

What size wire for a 200 amp subpanel?

3/0 AWG copper where the conductors and terminals are all rated 75 °C. Where anything is limited to 60 °C, copper goes to 250 kcmil, rated 215 A. In aluminum at 75 °C it is 250 kcmil, rated 205 A. A subpanel that serves only part of the home gets no 83% reduction under NEC 310.12, and continuous loads on it count at 125%.

Can I use 2/0 copper for 200 amps?

Only for a dwelling service or main feeder that carries the whole home's load under NEC 310.12, with 75 °C conductors and terminals. 2/0 copper is rated 175 A at 75 °C. That covers the 166 A the rule requires but not the full 200 A, so a 200 A subpanel feeder needs 3/0 copper.

How far can you run 3/0 copper at 200 amps?

About 239 feet one way at 240 V and the full 200 A before voltage drop passes 3%. Over 200 feet it drops 6.01 V, 2.51%, leaving 234.0 V at the panel. A smaller load can run further, because the drop scales with the current.