AWG sizes are defined by diameter, while metric cable sizes (IEC 60228) are named by cross-sectional area in square millimeters. The two series don't line up: 2.5 mm² sits between 14 AWG (2.08 mm²) and 12 AWG (3.31 mm²), at about 13.2 AWG.
Choose a gauge to see its exact area and the nearest metric size, or type an area in mm² to see the equivalent AWG and the smallest AWG at least that large. When substituting one system for the other, round to the larger wire, never the smaller: a smaller cross-section carries less current and drops more voltage.
Metric sizes in the table are the standard series from IEC 60228: 0.5, 0.75, 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50 mm² and up. Wiring rules outside the US set their own current ratings for these sizes, so use this page to compare sizes, not to rate a metric cable.