30 Amp Wire Size

10 AWG copper

For a 30 A breaker with NM-B cable (60 °C). Where the 75 °C column applies, such as THHN in conduit with 75 °C terminals, the size is the same: 10 AWG copper. In aluminum: 8 AWG at 60 °C, 8 AWG at 75 °C.

Smallest wire for a 30 A breaker, NEC 2026 Table 310.16 and 240.4(D). 30 °C ambient, up to three current-carrying conductors.
Wire and columnSmallest sizeAllowed amps
Copper, 60 °C10 AWG30 A
Copper, 75 °C10 AWG30 A
Aluminum, 60 °C8 AWG35 A
Aluminum, 75 °C8 AWG40 A

How length changes the answer

Recommended AWG for 30 A at 240 V single phase, by one-way length: the larger of the ampacity size and the size that keeps voltage drop within 3%.
Length, one way Copper, 60 °C Copper, 75 °C Aluminum, 60 °C Aluminum, 75 °C
25 ft101088
50 ft101088
75 ft101088
100 ft8866
150 ft8866
200 ft6644

Check your own circuit in the wire size calculator

Use this next

A 30 amp breaker takes 10 AWG copper or 8 AWG aluminum, and the answer is the same in NM-B cable and in conduit. 10 AWG copper is rated 30 A at 60 °C and 35 A at 75 °C, but NEC 240.4(D) caps it at a 30 A breaker either way, so the 75 °C column doesn't buy a smaller wire. 10 AWG aluminum is capped at 25 A, which leaves 8 AWG aluminum, rated 35 A at 60 °C.

A clothes dryer is the most familiar 30 A circuit in a home. The four-wire dryer receptacle is the NEMA 14-30: 30 A, 125/250 V, four wires, meaning two hots, a neutral and a ground. The 125/250 V rating means it supplies 240 V across the two hots and 120 V from either hot to the neutral, so the circuit needs all four conductors. In NM-B that is 10/3 cable: three insulated conductors plus the bare ground. You may also find a NEMA 10-30, the older three-wire type, which has two hots and a neutral but no ground. If you're replacing a dryer or its receptacle and find a 10-30, ask an electrician or your inspector how to handle it.

Electric storage water heaters are the other common 30 A circuit. NEC 422.13 has the branch circuit for a storage water heater of 120 gallons or less sized at 125% of the heater's rating. Working backward, a 30 A circuit covers a heater drawing up to 24 A, which is 5,760 W at 240 V. The nameplate decides, not the 30 A figure: a heater rated higher needs a larger circuit, and the installation instructions give the breaker the manufacturer calls for.

The NEMA TT-30 is the 30 A RV receptacle, and it is a different circuit: 125 V, not 125/250 V. That makes it a 120 V run, so the length table below, worked out at 240 V, understates its voltage drop. At 120 V and the full 30 A, 10 AWG copper reaches 3% at 49.4 feet one way, where the same wire at 240 V would go 98.8 feet. An RV pad 100 feet from the panel on 10 AWG would see a 6.07% drop at 30 A. For a TT-30 run, use the wire size calculator with 120 V selected.

A 30 A feeder to a small subpanel, in a shed or a detached garage, uses the same sizes: 10 AWG copper or 8 AWG aluminum. If the subpanel serves continuous loads, the feeder is sized at 125% of them, under 215.4(A)(1) (215.2(A)(1) in 2023). For an outbuilding the deciding factor is usually distance. At 240 V, 10 AWG copper stays within 3% out to 75 feet, the length table moves to 8 AWG at 100 and 150 feet, and to 6 AWG at 200 feet. A 150-foot run of 10 AWG at the full 30 A drops 10.93 V, which is 4.56%, past the 3% that an NEC informational note suggests (a recommendation, not a requirement).

Frequently asked questions

Can I use 12 gauge wire on a 30 amp breaker?

No. NEC 240.4(D) limits 12 AWG copper to a 20 A breaker, so it can't go on 30 A in any cable or conduit. 10 AWG copper is the minimum, or 8 AWG aluminum.

What size wire for a 30 amp subpanel?

10 AWG copper or 8 AWG aluminum for the feeder, then check the distance. At 240 V and the full 30 A, copper needs 8 AWG at 100 to 150 feet and 6 AWG at 200 feet to stay within 3%. Aluminum goes to 6 AWG at 100 to 150 feet and 4 AWG at 200 feet.

Do I need 10/2 or 10/3 wire for a dryer?

10/3 for a NEMA 14-30 dryer receptacle. The 14-30 is a four-wire 125/250 V device, so it needs two hots, a neutral and a ground, and 10/3 NM-B has three insulated conductors plus the bare ground. 10/2 has two insulated conductors plus the ground, which suits a load that runs on 240 V alone and needs no neutral.

What size wire for a 30 amp RV hookup?

10 AWG copper for a TT-30 receptacle on a short run. Because the TT-30 is 125 V, the drop builds twice as fast as on a 240 V circuit: at the full 30 A, 10 AWG copper stays within 3% only to about 49 feet, and 8 AWG to about 78 feet.

Is a 30 amp circuit enough for a water heater?

For a storage water heater of 120 gallons or less drawing up to 24 A, yes: NEC 422.13 sizes its circuit at 125% of the heater's rating, and 125% of 24 A is 30 A. That is 5,760 W at 240 V. A heater rated higher needs a larger circuit; the nameplate decides.