40 Amp Wire Size

8 AWG copper

For a 40 A breaker with NM-B cable (60 °C). Where the 75 °C column applies, such as THHN in conduit with 75 °C terminals, the size is the same: 8 AWG copper. In aluminum: 6 AWG at 60 °C, 8 AWG at 75 °C.

Smallest wire for a 40 A breaker, NEC 2026 Table 310.16 and 240.4(D). 30 °C ambient, up to three current-carrying conductors.
Wire and columnSmallest sizeAllowed amps
Copper, 60 °C8 AWG40 A
Copper, 75 °C8 AWG50 A
Aluminum, 60 °C6 AWG40 A
Aluminum, 75 °C8 AWG40 A

How length changes the answer

Recommended AWG for 40 A at 240 V single phase, by one-way length: the larger of the ampacity size and the size that keeps voltage drop within 3%.
Length, one way Copper, 60 °C Copper, 75 °C Aluminum, 60 °C Aluminum, 75 °C
25 ft8868
50 ft8868
75 ft8866
100 ft8866
150 ft6644
200 ft4433

Check your own circuit in the wire size calculator

Use this next

A 40 amp breaker takes 8 AWG copper, and at this rating the kind of wire doesn't change the copper answer. In NM-B cable, which NEC 334.80(A) holds to its 60 °C rating, 8 AWG copper carries exactly 40 A, with nothing to spare. With THHN in conduit and 75 °C terminals the same wire is rated 50 A, but no smaller copper size qualifies: 10 AWG is listed at 35 A in the 75 °C column, and 240.4(D) limits it to a 30 A breaker anyway.

Aluminum is where the column decides. At 60 °C, 8 AWG aluminum is rated 35 A, 5 A under the breaker, so the 60 °C size is 6 AWG, rated 40 A. In the 75 °C column 8 AWG aluminum reaches 40 A and qualifies. Both aluminum sizes land exactly on the breaker rating, with no margin above it.

Cooking is the code's own 40 A case. NEC 210.19(C) sets a 40 A minimum branch-circuit rating for a household range of 8¾ kW or more, and the 2026 NEC's Annex D works an 8,000 VA range demand (Table 120.55, Column C; 2023: Table 220.55) out to 33 A and supplies it with 8 AWG copper on a 40 A circuit. Ranges are commonly put on 40 A or 50 A circuits, but only the 40 A figure is a code minimum; the nameplate and installation instructions (110.3(B)) set what a given range needs. A separate cooktop or wall oven also falls under 210.19(C), but the 40 A minimum is written for ranges. One cooktop or one oven is figured at its nameplate rating (Table 120.55 notes; 2023: Table 220.55, Note 5).

For loads sized at 125%, a 40 A circuit is the match for 32 A. The 2026 NEC treats EV charging as a continuous load (625.41; 2023: 625.41 and 625.42), and the breaker and wire for a continuous load are sized at 125% of it under 210.20(A) and 210.19(A)(1). An EV charger set to 32 A therefore needs 32 × 1.25 = 40 A, while one set to 40 A needs a 50 A circuit. A storage water heater of 120 gallons or less is sized the same way under 422.13, so a 40 A circuit covers one drawing up to 32 A, which is 7,680 W at 240 V.

Air conditioners and heat pumps are sized from their nameplate, not from a breaker rating. Under Article 440 the nameplate gives a minimum circuit ampacity (MCA) and the maximum rating of the breaker or fuse, often shown as MOP or MOCP (440.4(B)). The wire has to carry at least the MCA, which already includes the 125% that 440.32 applies to a motor-compressor, so it isn't added a second time. The breaker or fuse may not exceed the marked maximum (440.22(C)). For this equipment the electrician starts from those two nameplate figures rather than from the tables on this page.

Length moves the copper size only on longer runs. At 240 V and the full 40 A, 8 AWG copper drops 6.11 V over 100 feet, 2.55%, and reaches 3% at about 118 feet one way. At 150 feet it would drop 3.82%, so the length table moves both copper columns to 6 AWG, which brings the drop to 2.40%; at 200 feet it is 4 AWG. Aluminum at 75 °C runs out sooner: 8 AWG aluminum reaches 3% at about 71 feet, which is why the table gives 6 AWG from 75 feet. The table puts the whole 40 A at the far end. A charger drawing 32 A drops a fifth less, and on 8 AWG copper it stays within 3% to about 147 feet. The 3% figure comes from an NEC informational note and is a recommendation, not a requirement.

Frequently asked questions

Can I use 10 gauge wire on a 40 amp breaker?

No. NEC 240.4(D) caps 10 AWG copper at a 30 A breaker, in NM-B and in conduit alike, even though Table 310.16 lists it at 35 A in the 75 °C column. A 40 A breaker needs 8 AWG copper or larger, or 6 AWG aluminum at 60 °C (8 AWG aluminum at 75 °C).

Is 8 gauge wire good for 40 amps?

Yes, in copper and in every column: 8 AWG copper is rated 40 A at 60 °C, which covers NM-B, and 50 A at 75 °C. At 240 V and the full 40 A it stays within 3% voltage drop to about 118 feet one way; the length table gives 6 AWG copper at 150 feet.

What size wire for a 40 amp range circuit?

8 AWG copper. NEC 210.19(C) sets a 40 A minimum circuit for a household range of 8¾ kW or more, and the 2026 NEC's own Annex D example supplies an 8,000 VA range demand with 8 AWG copper on a 40 A circuit. Whether a particular range needs 40 A or 50 A comes from its nameplate and installation instructions.

What breaker and wire does a 32 amp EV charger need?

A 40 A breaker with 8 AWG copper. EV charging is a continuous load, so the circuit is sized at 125% of the charger's current: 32 × 1.25 = 40 A. The 2026 NEC places this in 625.41 and 210.20(A) (2023: 625.41 and 625.42).

What size aluminum wire for 40 amps?

6 AWG aluminum at 60 °C, or 8 AWG where the 75 °C column applies; both are rated 40 A. At 240 V and the full 40 A, keeping within 3% takes 4 AWG aluminum at 150 feet and 3 AWG at 200 feet, in both columns.